- CTS Combi bus 2x2x0,34+2x1,50 brown
- H05BQ-F / H07BQ-F
- JMV Railroad cable AL-S
- JMV Twin Battery (Radaflex)
- Combi Cable HF
- LIFT2TY
- NKXS-Ftn (Railroad cable armoured)
- RG 59 Coax B/U Petro
- Robot cable PUR
- TML Round (Drinking water cable)
- Y-JZ UV
- Bare copper
- Fireproof cables according to IEC 60331
- Bus cables
- Data-, fiber-, and coax cables
- EMC cables
- Rubber cables
- Halogen-free installation cables
- Halogen-free control and signal cables
- Instrument cables
- Cable set
- Cable accessories
- Cables for charging stands
- Marine cables
- Medium voltage cables
- Mounting cables and wires
- Petro installation cables
- PVC installation cables
- PVC control and signal cables
- Solar cables
- Telecom cables
- High temperature cables
- Heating cables
NKXSAL-Ftn 19×2,5mm2 RE 300/500v black
Information
EAN no. : | 5710693091623 |
---|---|
Item no. : | 703419026-08 |
Product name: | NKXSAL-Ftn 19x2,5mm2 RE 300/500v black |
Unit: | m |
Number / cross-section mm²: | 19 × 2,5 |
Packaging: | Tr |
Colour: | Black |
Diameter approx. mm: | 22,3 |
Weight, kg/km: | 811 |
Description
Application
NKXSAL-Ftn is an armored and shielded railroad cable, which can be used as a fixed installation cable indoors as well as outdoors. The cable provides good protection against rodent attacks and other mechanical challenges.
Mechanical Design
Conductor: | Solid copper RE class 1 according to EN60228 |
Insulation: | XLPE. |
Screen: | Aluminium/polyester tape |
Inner sheath: | Thermoplastic halogen-free compound |
Screen: | 2 layers of galvanized steel tape, with overlap.
Thickness: 0,2mm. |
Outer sheath: | Thermoplastic halogen-free compound, UV-resistant, black. |
Conductor colors: | White leaders with black numbers. |
Technical specifications
Max. conductor temperature: | + 90 ° C |
Handling temperature: | -30° C to +70° C permanently installed. |
Installation temperature: | -5° to + 40° |
Short circuit temperature maximum: | 250 ° C |
Test voltage: |
2000v AC |
Rated voltage: |
300/500v AC |
Bending radius: | 15 x D |
Standards:
EN 61034-2 (IEC 61034-2) / EN 60332-1-2 (IEC 60332-1) |
EN 60228; EN 50288-7, DS 2393-3 |
EN 50267-2-1 (IEC 60754-1): <0,5% acid gas. |
EN 50267-2-2 (IEC 60754-2): pH³ 4,3; conductivity ≤10 mS/mm |