- (N)2XS(F)H 6/10kV
- (N)2XSY PEX 12/20 kV
- AXQJ RMF Pure 12 kV
- AXQJ RMF Pure 24 KV
- JMV (N)2XSH
- JMV AL-S NA2XSEH
- JMV N2XS(FL)2Y 60 kV
- JMV NA2XS(FL)2Y
- JMV PEX-M-AL-LRT
- JMV PEX-M-AL-LT
- N2XSEY 6/10(12) kV RT
- NA2XS(F)2Y 12/20 kV
- NA2XS(F)2Y 6/10 kV
- NA2XSY 12/20kV
- PEX-AL DK 12kV
- PEX-AL HF 24 kV black
- Bare copper
- Fireproof cables according to IEC 60331
- Bus cables
- Data-, fiber-, and coax cables
- EMC cables
- Rubber cables
- Halogen-free installation cables
- Halogen-free control and signal cables
- High voltage cables
- Instrument cables
- Cable set
- Cable accessories
- Cables for charging stands
- Marine cables
- Mounting cables and wires
- Petro installation cables
- PVC installation cables
- PVC control and signal cables
- Solar cables
- Special cables
- Telecom cables
- High temperature cables
- Heating cables
JMV PEX-AL-S 12kV 3×150/25 mm2 HF SE red
Information
| EAN no. : | 5710693056370 |
|---|---|
| Item no. : | 37830315025 |
| Product name: | JMV PEX-AL-S 12kV 3x150/25 mm2 HF SE red |
| Unit: | m |
| Number / cross-section mm²: | 3 × 150/25 |
| Packaging: | Tr 500 |
| Colour: | Red |
| Diameter approx. mm: | 55 |
| Weight, kg/km: | 2769 |
Description
Application
JMV PEX-AL-S 12 kV is a halogen-free medium voltage cable, which can be used as a supply cable in distribution networks and in buildings. The cable is approved for direct burial in the ground. It can withstand voltage up to 12 kV.
After each cut, the cable ends must be sealed against moisture.
Construction
| Conductor: | Solid sector-shaped aluminum conductor cl. XNUMX |
| Manager screen: | Extruded semiconductor |
| Insulation: | XLPE, superclean vulcanized extruded |
| Insulation screen: | Stripable |
| Screen: | Creepet carbon paper, copper wire in counterspiral with copper ribbon wrapped with clear foil. |
| Outer sheath: | PE, MDPE, UV-stabilized. Halogen-free. |
| Color: | Red |
| Conductor marking: | 1-2-3 in white print |
Technical specifications
| Test voltage: | 30.000 volts AC from conductor to screen for 5 min. |
| Rated voltage: | 12 kV |
| Max operating temperature: | + 90 ° C |
| Max short circuit temp: | + 250 ° C |
| Mine. handling temp: | - 5 ° C |
| Permissible bending radius: | 10 x the diameter of the cable |
Standards:
| IEC 502 and HD 620 part 10D |
| VDE 0276 620 |